|
|
|
How SuperHeat 5 checks for compliance with Elemental,
Calculation and Heat Loss methods
Checking for compliance with Elemental, Calculation and Heat
Loss methods using the 2002 Part L and Part J documents is more complicated
than before, because different U-value standards are applied to openings with
metal and non-metal (wood or uPVC) openings. A decision has to be made as to
how to handle cases where there is a mixture of frame types. This page sets out
the methodology we have introduced into SuperHeat 5.00d (revised in 5.01). We
do not pretend that this is the only way of approaching this subject and will
gladly consider any alternative approaches.
Elemental method
First consider a house with a floor area of 100m². The combined area of
windows and rooflights may not exceed 25% of the floor area (25m²) as long
as the average U-values of metal and non metal framed openings are 2.2 and 2.0
or less respectively (the heating system is assumed to come within Table 1).
|
Case
(MO:metal framed opening area; NMO: non-metal framed do.;
MUV: metal framed opening average U-value; NMUV: non-metal do.)
|
How SuperHeat 5 treats it when checking for Elemental Method
compliance
Where the building fails using the Elemental Method it may
be possible to show compliance using the Target U-Value or Carbon Index
methods
|
|
MO+NMO<=25;
MUV<2.2; NMUV<2.0
|
OK Full compliance
|
|
MO+NMO>25;
MUV<2.2; NMUV<2.0
|
Fail (opening area cannot exceed stated value regardless of
U-value)
|
|
Scotland: MO+NMO<=25;
MUV>2.2 or NMUV>2.0
|
Fails (average U-values must not exceed Elemental limits)
|
|
E&W: MO=22; MUV=2.4
|
Additional heat loss through 25m² metal framed windows with UV=2.2 in
walls with a UV=0.35 would be 25x(2.2-0.35) = 46.25 W/K.
Additional heat loss through 1m² of window with UV=2.4 =
(2.4-0.35)=2.05 W/K.
Permissible window area = 46.25/2.05 = 22.56m². Actual = 22
OK
|
|
E&W: NMO=22; NMUV=2.4
|
Additional heat loss through 25m² non metal framed windows with UV=2.0
in walls with a UV=0.35 would be 25x(2.0-0.35) = 41.25 W/K.
Additional heat loss through 1m² of window with UV=2.4 =
(2.4-0.35)=2.05 W/K.
Permissible window area = 41.25/2.05 = 20.12m². Actual = 22
Fail
|
|
E&W: NMO=4; NMUV=2.4; MO=18; MUV=2.4
|
See working above: with these opening average U-values you can have
22.56m² of metal framed openings or 20.12m² of non
metal framed openings. If the combined proportions of actual/permissible are
1.0 or less then the building complies:
4/20.12+18/22.56 = 0.997 OK
|
|
E&W: NMO=18; NMUV=2.4; MO=4; MUV=2.4
|
See previous calculation. New ratio is
18/20.12+4/22.56 = 1.072 Fail
|
Calculation/Heat Loss method (buildings other than
dwellings)
The Calculation Method in earlier Part L AD's no longer officially has this
name but it is still there as in L2 §1.15 as a variation on the
Elemental Method, and renamed as the Heat Loss method in Part J (Scotland). In
each case the actual building is compared with a notional building of the same
shape and size as the actual building with solid elements constructed to
Elemental Method standards (with the caveat that where the U-value of an
uninsulated ground floor of this size and shape is lower, the lower figure is
used.
The total area of door, window and roof light openings allowed by the
Elemental Method (15/30/40% of external wall area + 20% of roof area)
determines the door/window and rooflight areas in the notional building - see
the table below - and (except in NI) whether a check has to be made on the
average U-values of opaque elements. If (except in NI) the total opening area
is below the Elemental Limit, the average U-value of each element has to
be no more than the Elemental limit + 0.02. So in such cases you can trade off
(for example) a piece of wall with a U-value of 0.4 against a similar area with
a U-value of 0.3, or use windows with a higher U-value than the Elemental
figure, but cannot use the reduced opening area to allow a higher U-value for
opaque elements or use a higher than minimum level of insulation in the walls
to compensate for an uninsulated solid floor with a U-value of more than 0.27.
Our understanding is that these rather convoluted requirements are based on the
fact that later insulation improvements to walls and floors (and some roofs)
may be almost impossible, whilst replacing windows with ones of a higher
standard is much easier in most cases.
A further complication (except in NI) is that the Elemental U-value figures
for doors, windows and rooflights vary depending on whether wood/uPVC or metal
frames are used. Where the actual building has a mixture of frame types we take
the proportions and use a weighted average for the U-value of the openings in
the notional building: for example if the building has windows of 50% of each
frame type, the notional building window U-value is taken as 2.1 (2.0x50% +
2.2x50%)
The effect of these various assumptions is that if you enter a building that
just meets the Elemental requirements with the doors, windows and rooflights
using any mixture of metal and non-metal frames and with the rooflights
distributed between different roof types in any proportion, the calculated heat
loss for the notional building will be exactly the same as for the actual
building and this is our justification for approaching the problem in this way.
|
|
England & Wales L2 1.16
|
Scotland - Heat Loss Method: J8.5, J8.6
|
Northern Ireland
|
|
Actual area of doors, windows and rooflights as compared with Elemental
Allowance
|
More
|
Less
|
More
|
Less
|
More
|
Less
|
|
Window area
|
As Elemental Method 15/30/40% of external wall area
|
Actual area
|
|
Rooflight area - actual building has rooflight(s): one type of roof (e.g.
flat roof) only
|
20% (EM) of roof
|
Actual area(s)
|
|
Assumed window U-value (non-metal/metal frame)
|
2.0/2.2
|
3.3
|
|
Assumed rooflight U-value (non-metal/metal frame)
|
2.2/2.2
|
2.0/2.2
|
3.3
|
|
Rooflight area - actual building has rooflight(s). More than one roof type
(e.g. some flat, some pitched)
|
Multiply each rooflight area in actual building by SARx20%/SARL. For example if a building has 50m2 of
pitched roof with 5m2 of rooflights, and 50m² of flat roof with 7.5m²
of rooflights the actual areas are multiplied by 100x0.20/12.5 = 1.60 - so the
notional building is given 8m² of rooflight in the flat roof and 12m²
in the pitched roof.
|
Actual area(s)
|
|
Rooflight area - actual building has no rooflight(s)
|
20% (EM) of each roof area taken as rooflight (see examples in
L2 App.E, Part J App.H and Part F App.H)
|
None
|
|
Maximum U-value of any external wall or exposed floor
|
0.70
|
0.70
|
0.70
|
|
Maximum average U-value of all external walls
|
None
|
0.37 (0.35+0.02)
|
None
|
0.32 (0.30+0.02)
|
None
|
|
Maximum U-value of any roof
|
0.45
|
0.45
|
0.7 (0.45 if residential)
|
|
Maximum average U-value of other elements
|
None
|
EM+0.02
|
None
|
EM+0.02
|
None
|
|
|